»  Fiche produit Retour aux résultats








Centrale adressable - (FS6000)

FIRE ALARM LINES

Maximum number of linear modules
4
Number of fire alarm lines (loops) in a module
4(2)
Maximum number of addresses in a line (loop)
127
Maximum resistance of the two-wire fire alarm line
40Ω
Output resistance
20Ω
FIRE ALARM AND INTERLOCKING OUTPUTS

Open collector type 30V/0.3A
8
Relay, potential-free, switching 250V/8A
10
Controllable, relay, potential (25-35)V (require end-of-line module)
2
FUNCTIONAL DESCRIPTION

Light indication for Test mode
Green
Light indication for Night mode
Red
Common purpose liquid crystal display
4 lines x 20 symbols
Built-in sound alarm for fire condition
Two-tonal
Built-in sound alarm for fault condition
One-tonal, discontinuous
Built-in real time clock
Yes
Selection of test and setup modes
Yes
Energy independent archive of events, registered by the system, containing event’s type, date and time
200 events
Communication interface for external devices
RS 232
POWER SUPPLY

Mains
220V / 50Hz
Backup battery
24V / 7Ah
Consumption on battery
< 400mA
Dimensions
360 x 490 x 110 mm
Weight (batteries not included)



 

ALLEM SECURITY  
 
Téléphone : +216 71 835 522
 
  Vitrine de l'entreprise
  Coordonnées de l'entreprise
Contacter l'entreprise
Votre message
Sujet:
Message:
Si vous n'êtes pas inscrits cliquez ici
Votre compte

E_mail (login)
* (L'adresse e-mail doit impérativement être correcte)
Mot de passe * (6 caractéres min)
Retaper mot de passe *
Civilité/Nom/Prénom
Nom de la société *
Téléphone *
Fax
Taper ces caractères
Si vous êtes déjà inscrits tapez votre login et mot de passe